LSA R & LSA H - 49.1

LSA R & LSA H - 49.1

LSA R and LSA H
Power 350 - 530*
Voltage 380 - 440V
Poles 4
Speed 1500 - 1800 rpm
?Shaft height ?400 mm
??Max efficienc??y ??96.7 %
?Excitation ?AREP
?Regulation ?R450?
* kVA/50Hz - kW/60Hz | Continuous / 40°C
(Discrepancies may occur, consult catalogue for exact figures)


? Benefits ? Key Features
? Downloads ? Options
? Regulation  


Back to topApplications

?Commercial application
Commercial
?Industrial application
Industrial
?Powerplant application
Powerplants
?Marine application
Marine

Back to top
Benefits

The LSA R and LSA H are enclosed alternators (IP 55).

  • LSA R cooling is performed by an air/air exchanger (cooling index: IC 6.A1.A1 in accordance with IEC 60034-6 standard).
  • LSA H, cooling is performed by an air/water exchanger (cooling index: IC 8.A1.W7 in accordance with IEC 60034-6 standard).

These alternators can be ATEX (Explosive Atmosphere) certified in accordance with EEXem II T3 protection. 
 

DownloadsBack to top

 

Back to topKey features

Insulation class H
Winding pitch 2/3 (winding 6S)
Number of wires 6
Protection IP 55
Altitude ≤ 1000 m
Overspeed 2250 min-1
Excitation system / AVR type AREP  / R450
Voltage regulation (Steady state) ± 0,5%
Short-circuit current (3 IN / 10 s) 300 % (3 IN) : 10s
Totale Harmonic distortion THD at no load < 4 % - on load < 4 %
Waveform: NEMA = TIF < 50
Waveform: I.E.C. = THF? ?< 2%

??

Back to topRegulation?

??????????????????????????????

OptionsBack to top

  • Other voltages available (specific windings).
  • Space heater.
  • Winding protection for harsh environments and relative humidity above 95%.
  • Specific cable outlet.
  • Temperature detectors.
  • Thermal protection for winding and shields.
  • Remote Voltage Trimmer.
  • Filters on air inlet: derating 5%.
  • IP 44 Filters on air inlet and air outlet : derating 10%.
  • Lower shaft height on demand.?
  • Two bearing.
  • Customizable Painting.?
???????????????